4-digit backlit LCD display (6,000 counts) · Measurement of leakage, differential, protective conductor, and load currents in electrical systems, devices, and machines · Measurement without shutdown under normal operating conditions · Ideal for preventive maintenance and troubleshooting (protection against property damage, personal injury, power outages, etc.) · Reliable and easy detection of insulation faults (e.g., defective cables, loose terminals, contamination, moisture) · Frequency characteristic according to EN 61557-16 for testing electrical devices according to VDE 0701-0702 · LPF low-pass filter (40 - 70 Hz) for suppressing high-frequency interference signals · Frequency range for rail and industry: 15 Hz - 1 kHz (fg) · Defined protection against external magnetic fields according to EN 61557-13, Class 2 = 30 A/m · Automatic range selection · Peak value (PEAK), measured value memory (HOLD) · Zero adjustment (ZERO) · Jaw opening max. 23 mm · Measurement category CAT IV 300 V, CAT III 600 V · Measurement ranges: AC current (0.010 mA - 60 A), highest resolution of 1 µA in the 6 mA measurement range, voltage (0.01 V - 600 V AC/DC), resistance (0.1 Ω - 600 kΩ), continuity test Further technical features: · Width: 76mm · Length: 210mm · Height: 34mm · Display: LCD